Technical Datasheet for Reverse Osmosis System (1,000LPH) and Water Treatment Plant

Reverse Osmosis System

Capacity                                         1000 ltr/hr

Inlet connection                             1”

Outlet connection                          1”

Drain Connection:                         1”

Recovery: Max.                             80%   

Power Supply/Consumption         220V 50hz single phase/ 1.8kW Max

4pcs of 4040 Membrane

304 Stainless Steel 4040 Membrane Housing

1HP Stainless surface pump

2HP Vertical pump

Long Cartridge Filter

Permeate / concentrate Flow Meters

Attached PVC Fittings

304 Stainless Steel Body frame

  1. Multigrade Filter (MGF) FRP Vessel 18” with Media

Specification

Details

Vessel Type

FRP (Fiberglass Reinforced Plastic)

Diameter

18 inches

Height without base

65”

Capacity

253L

Media Type

Multigrade filter media

Inlet/Outlet Size

4”

Application

Fe/Mn removal, Arsenic, Selenium removal

Features

High filtration efficiency, Easy maintenance, Corrosion-resistant construction

  1. Fe/Mn Removal Filter and Ion Exchange Resin Filter FRP Vessel 18” with Media

Specification

Details

Vessel Type

FRP (Fiberglass Reinforced Plastic)

Diameter

18 inches

Height

65”

Media Type

Akdolit®, Greensand and Ion Exchange Resin

Capacity

253L

Inlet/Outlet Size

1”

Application

Specialized media for Fe/Mn or Arsenic/Selenium removal

Features

Effective contaminant removal, Durable and reliable design

  1. Activated Carbon Filter (ACF) FRP Vessel 18” with Media

Specification

Details

Vessel Type

FRP (Fiberglass Reinforced Plastic)

Diameter

18 inches

Height

65”

Media Type

Activated carbon

Capacity

253L

Inlet/Outlet Size

1”

Application

Removal of residual chlorine byproduct, taste, and odor

Features

High adsorption capacity, Long service life

  1. Pre-Filtration Chlorination Diffuser with 20 pcs Chlorine Tablets Supply

Specification

Details

Type

Pre-Filtration Chlorination Diffuser

Chlorine Tablets

20 pcs

Application

Disinfection of feed water

Features

Efficient chlorine dispersion, Easy to replace tablets

 

  1. Long UV Disinfection Tube

Specification

Details

Type

UV Disinfection Tube

Inlet/Outlet

1”

Power Rating

220V-240V AC”:50/50Hz, UV30W

Max Flow Rate

8GPM

Application

Disinfection of water

Features

Effective pathogen removal, Low energy consumption

  1. 2 Nos of 1HP Filtration & Booster Pump – InterDAB

Specification

Details

Type

Filtration & Booster Pump

Model

InterDAB

Power

1 HP

Application

Water filtration and boosting

Features

Reliable performance, Compact design

  1. 2 Nos of 2,000L Potable Drinking Water Storage Tanks

Specification

Details

Type

Potable Drinking Water Storage Tank

Capacity

2,000 Liters

Material

PVC

Application

Storage of pre-treated and treated water

Features

Fit for drinking water, Durable construction, UV resistant

  1. PVC Plumbing Connections

Specification

Details

Type

1” PVC Plumbing Connections

Application

Connections for water flow

Features

Corrosion resistant, Easy installation